For correction to Power Factor of 0.95 of 415v 3 phase 4 pole motors with average characteristics.
|
MOTOR SIZE |
CORRECTION |
CAPACITOR FUSING |
|
3.0 |
1.5 |
4 |
|
4.0 |
2.0 |
4 |
|
5.5 |
2.5 |
6 |
|
7.5 |
3.0 |
6 |
|
11 |
5.0 |
10 |
|
15 |
6.25 |
16 |
|
18.5 |
8.0 |
16 |
|
22 |
10.0 |
20 |
|
30 |
12.5 |
25 |
|
37 |
15.0 |
32 |
|
45 |
15.0 |
32 |
|
55 |
20.0 |
40 |
|
75 |
20.0 |
40 |
|
90 |
25.0 |
50 |
|
110 |
25.0 |
50 |
| 132 |
30.0 |
63 |
|
150 |
35.0 |
80 |
|
185 |
40.0 |
80 |
|
220 |
45.0 |
100 |
|
250 |
50.0 |
100 |